Jumper setting

Jumper settings for Didactum CAN units and CAN expansion units.

When using the CAN bus ports of the Didactum Monitoring Systems, the terminator on the main unit (TERM) must be set to "ON".

On the Didactum main units and CAN expansion units, you will find a two-position DIP switch labeled "TERM". As a general rule, the terminator jumper is always the one of the two switches closest to the CAN bus ports.

The last CAN bus device (CAN sensor or CAN unit) in the serial CAN bus chain must always be terminated. Therefore, set the terminator to "ON".

Before setting the terminator switch, the corresponding Didactum CAN bus device must always be disconnected from the power supply or cable connection.

Terminator settings for Didactum CAN units

The graphic below applies to the following Didactum CAN-Bus devices:

  • Didactum Rack Monitoring Unit
  • Didactum Sensor Expansion Unit

Didactum CAN-Bus Dry Contact Expansion Unit

The following terminator setting applies to the Didactum CAN-Bus Dry Contact expansion unit:

Didactum CAN Sensor for Temperature, Humidity and Smoke

The following applies to the Didactum CAN sensor for temperature, humidity and smoke:

This website uses cookies

This website uses cookies to improve user experience. By using our website you consent to all cookies in accordance with our Cookie Policy.

Essential cookies enable basic functions and are necessary for the website to function properly.
Statistics cookies collect information anonymously. This information helps us to understand how our visitors use our website.
Marketing cookies are used by third parties or publishers to display personalized advertisements. They do this by tracking visitors across websites.