Activity LED
The TCP/IP-based monitoring devices are equipped with several LED status lights on the front panel. We will now explain the function of these status messages.
Activity indicator
Description: appliance status
For all Didactum Units.
| LED | Color | Mode | Function (Percentage Indication) |
|---|---|---|---|
| ACT / Activity | Green | Normal mode | The LED is active (ON) 50 % of the time, inactive (OFF) 50 % of the time. |
| Recovery mode | The LED is active 25 % of the time per cycle, inactive 75 % - fast blinking. | ||
| Error, stuck | The LED remains at 100 % ON or 0 % (OFF) - indicating a device freeze or boot failure. |
Error LED
Description: errors and activity.
For all Didactum Units.
| LED | Color | Mode | Function (Percentage Indication) |
|---|---|---|---|
| ERR / Error | Red | Normal mode | 0 % activity (OFF) — no error. 100 % ON (constant glow) — error present. |
| One-time activity | Brief 100 % ON pulse (single flash, approx. 0.1–0.5 sec) for restart of failed service or USB backup. | ||
| Software update mode | The LED blinks with a 50 % ON / 50 % OFF duty cycle at high frequency (2 Hz blink rate). | ||
| Recovery mode | The LED remains 100 % ON (solid) after 5 seconds of holding the RECOVERY button — recovery active. |
CAN LED
Description: CAN bus status.
For all Didactum Units.
| LED | Color | Mode | Function (Percentage Indication) |
|---|---|---|---|
| CAN / CAN status | Green | Normal mode | The LED shows different states according to communication status: • Slow blinking (25 % ON / 75 % OFF) - not connected to CAN devices. • Fast blinking (50 % ON / 50 % OFF) - CAN configuration in progress. • Constant glow (100 % ON) - successfully connected to CAN devices. |
LAN port LEDs
Description: Ethernet 10/100 Base-T port status.
For all Didactum Units.
| LED | Function | Color | Description (Percentage Indication) |
|---|---|---|---|
| LED0 | Link | Yellow | Variable activity: 10–90 % ON duty cycle during network activity. |
| LED3 | 100M | Green | 0 % (OFF) - 100 Mbps connection established. 100 % ON (solid) - no connection. |
Applicable for: 100T, 500T and 550T.
| LED | Function | Color | Description (Percentage Indication) |
|---|---|---|---|
| LED0 | Link | Yellow | Variable activity: 10–90 % ON duty cycle during network activity. |
| LED3 | 100M | Green | 100 % ON (solid) - 100 Mbps connection established. 25–50 % blinking - connection attempt. 0 % (OFF) - no connection. |
RS-485 Modbus RTU LEDs
Description: RS-485 Modbus RTU status.
Applicable for: 100T, 300T, 500T and 550T.
| LED | Color | Function (Percentage Indication) |
|---|---|---|
| RS-485 status | Red | 10-50 % ON duty cycle — Data transfer active. |
| Green | 10-50 % ON duty cycle — Data receiving active. |
OSDP reader LEDs
Description: RS-485 Modbus RTU status.
Applicable for: 100T, 300T, 500T and 550T.
| LED | Color | Function (Percentage Indication) |
|---|---|---|
| RS-485 status | Red | 10–50 % ON duty cycle - data transfer active. |
| Green | 10–50 % ON duty cycle - data receiving active. |
12V Output LEDs
Description: 12V outputs status.
For all Didactum Units.
| LED | Color | Description (Percentage Indication) |
|---|---|---|
| E1, E2 / Electronic Relays Outputs: 12 V DC, 0.25 A | Yellow or Orange | 100 % ON (constant glow) - relay is ON. 0 % (OFF) - relay is OFF. |
Outlet LEDs
Description: 110/240V IEC-320 C13 outlets.
Applicable for: Didactum PDU.
| LED | Color | Description (Percentage Indication) |
|---|---|---|
| OUT 1, …, OUT 8 | Yellow or Orange | 100 % ON (constant glow) - outlet is ON. 0 % (OFF) - outlet is OFF. |
NC/NO/COM power relay terminal LEDs
Description: 110/240V IEC-320 C13 outlets.
Applicable for: 500T and 550T.
| LED | Color | Description (Percentage Indication) |
|---|---|---|
| R1, R2 (Relay 1, Relay 2) | Yellow or Orange | 100% ON (constant glow) - relay is ON. 0% (OFF) - relay is OFF. |